It won't charge, or charges very slowly, in winter
Lithium iron phosphate cells shouldn't be charged hard when they're cold, so the BMS limits charging at low temperature. In an unheated garage or outbuilding this is the most common winter complaint. In the viewer, look at the temperature column: if the cells are close to freezing, slow or blocked charging is the battery protecting itself, not a fault. Moving the batteries somewhere warmer usually solves it.
One battery is always lower than the others
The stack table shows each battery's charge and voltage. If one unit ends each evening a few percent lower, or reaches full later, check the obvious first: the link cables between batteries and the power cables, which should be the same length and well tightened. If the cabling is fine and the gap keeps growing, write down the numbers over a week and talk to your installer.
A large cell spread
A spread of more than about 100 mV at rest, or one that grows week after week, points to a battery that isn't balancing well or a weaker cell. Our cell voltage guide explains what's normal. A few full charges often help, since balancing happens near full.
A battery goes offline or shows "Absent"
If a battery that used to appear in the stack table now reads Absent, the master can't see it any more. Usually that's a loose or faulty link cable, a DIP-switch address that changed, or a battery that switched itself off after a protection event. Check the cables and the battery's power button and LEDs first.
Alarms and protection flags
In the console, the status columns read Normal when all is well. Anything else (a voltage, current or temperature flag) shows up in the viewer's Alarms column, in the battery's own words. Note the exact text, the time and what the system was doing (charging hard, very cold, heavy load). That's exactly what an installer will ask you for.
The charge percentage jumps or looks wrong
The state of charge is estimated by counting energy in and out. It drifts over time and gets corrected when the battery reaches full. If the percentage seems off, a full charge every so often usually puts it right. A sudden jump right after reaching full is that correction, not a fault.
The console doesn't answer at all
Wrong socket, wrong cable type, another program using the port, or a console asleep after a power cut. The troubleshooting section of the online viewer goes through each one.
When to call your installer
- A protection alarm that keeps coming back.
- A cell or a battery that keeps drifting further away from the others.
- A battery that stays Absent after you've checked the cables.
- Any physical sign: heat, smell, swelling, a battery that won't switch on.
Bring the raw console text (the online viewer lets you download it) or share a read-only guest link from a Pylon-Monitor box: real numbers make the conversation much shorter.