Free · runs in your browser · nothing to install
Read your battery now
Read-only: the tool only sends the console commands pwr, bat, info and stat. Everything stays in your browser; nothing is uploaded.
Battery stack (pwr)
Cells of the master battery (bat)
Identity (info)
Counters (stat)
Raw console text
What you need
- A computer running Windows, macOS, Linux or ChromeOS, with Chrome, Edge or Opera. These browsers can talk to a serial port. Firefox and Safari can't, and neither can phones.
- A USB console cable for Pylontech: USB on one end, an RJ45 plug on the other, with an RS232 converter in between, wired for the Pylontech console. They're sold as "Pylontech console cable" or "BatteryView cable". See which cable to buy.
- The cable goes into the CONSOLE socket of the master battery. Not LINK PORT 0/1 (those link the batteries together), not CAN or RS485 (those go to the inverter).
Step by step
- Plug the cable into the laptop first, then into the CONSOLE port of the master battery. On Windows, wait a few seconds for the driver to load.
- Close BatteryView or any other serial program. Only one program at a time can open the port.
- Click "Connect the battery" above, pick the cable in the list (often "USB Serial", "FT232R", "CH340" or "PL2303") and confirm.
- The tool opens the port at 115200 baud, sends
pwr,bat,infoandstat, and lays out the answers: one row per battery, then the cells of the master battery. - Tick Refresh every 10 s to watch the battery live, or download the raw text to keep or to send to an installer.
Reading the results
The stack table
Each row is one battery, numbered by its position in the stack (1 is the master). Lowest cell and Highest cell are the weakest and strongest of its 15 or 16 cells; Spread is the difference between them.
- A spread under about 30 mV at rest is healthy.
- Between 30 and 100 mV, keep an eye on it. It often shrinks after a few full charges.
- Spreads above 100 mV, or one cell clearly lower than the others day after day, are worth showing to your installer.
States and alarms
Charge, Dischg and Idle are the normal working states. The voltage, current and temperature status columns read Normal when all is well; anything else (for example a low-voltage or high-temperature flag) is shown in the Alarms column, in the battery's own words.
Cells
The cell grid shows every cell of the master battery, coloured from the lowest to the highest. A cell marked balancing is being trimmed by the BMS, which is normal near full charge.
If nothing shows up
- "No answer from the battery": first check the socket. CONSOLE is easy to confuse with the neighbouring ports. Then make sure the battery is switched on (the power button lit).
- Some batteries keep their console asleep after a power cut and only wake up when they receive a special sequence at 1200 baud. BatteryView sends it; this tool sends it too, automatically, when the first attempt gets no answer.
- "Port already in use": BatteryView, PuTTY, an inverter tool or a second browser tab still has the port open. Close it and try again.
- The cable isn't in the list: on Windows, install the driver of the chip in your cable (FTDI, Prolific or CH340). On Linux, your user must be allowed to use serial ports (the
dialoutgroup). - Garbled characters: the cable is probably a plain RS485 adapter or a network cable. The Pylontech console needs RS232 levels.
Is it safe for the battery?
Yes. The tool sends four read-only commands, the same ones you would type by hand in a terminal. It doesn't send configuration commands or write to the BMS, and it leaves the link with your inverter alone. Nothing is uploaded either: the data goes from your cable to your screen and stays there, so download the text if you want to keep it.
Prefer to see it on your phone?
A laptop on the garage floor is fine for a check-up, but nobody wants to do that every day. The Pylon-Monitor V3 box plugs into the same CONSOLE port and shows the same figures on its own screen, on your phone and in Home Assistant, without you lifting a finger.