The battery
LFP (LiFePO4)
Lithium iron phosphate, the cell chemistry used in Pylontech home batteries. It is known for long life and stability, and for a very flat voltage curve.
BMS
Battery management system: the electronics inside each battery that measure every cell, protect them, balance them and talk to the inverter. A viewer reads what the BMS reports.
Cell
One of the individual units inside a battery. A US2000C, US3000C or US5000 has 15 cells in series. See what normal cell voltages look like.
SOC (state of charge)
How full the battery is, in percent. The BMS estimates it by counting energy in and out, and corrects it when the battery reaches full.
SOH (state of health)
How much of its original capacity a battery still has, in percent, as estimated by the BMS. Shown by the stat command.
Cycle count
The number of charge–discharge cycles the battery has counted. Together with SOH, it is the best quick indicator of a battery's age.
Balancing
The BMS bringing its cells to the same voltage, mostly near full charge. A cell being balanced is shown as BAL = Y by the bat command.
Cell spread
The difference between the highest and lowest cell voltage of one battery. Small and stable at rest means a healthy, well-balanced battery.
Protection
What the BMS does when a limit is reached: it reduces or stops charging or discharging, for example when a cell is too high, too low or too cold. Protection states appear in the console status columns.
The stack
Master battery
In a group of linked batteries, the one that talks to the inverter and reports for the whole stack. A viewer connects to the master only.
Slave battery
Any other battery in the stack. It reports to the master through the link cables.
Address and DIP switch
Each battery has a position in the stack (1 for the master, then 2, 3…). The small switch block marked ADD sets how the battery is addressed; a wrong setting can make a battery appear as Absent.
Ports and cables
CONSOLE port
The service port on the front of the battery, used by BatteryView, our online viewer and the Pylon-Monitor box. It speaks RS232 at 115200 baud. See which cable to use.
LINK PORT 0 / 1
The sockets that chain batteries together so the master can see the others. They are not for viewers or inverters.
CAN and RS485 ports
The ports the master uses to talk to the inverter, so it knows how much it may charge and discharge. Reading the CONSOLE port does not interrupt this link.
RS232
The type of serial signal used by the CONSOLE port. A USB-RS485 adapter or a network cable won't work in its place.
Baud rate (115200 / 1200)
The speed of the serial link. The console normally runs at 115200 baud; after a power cut some batteries start in a 1200-baud protocol mode and need a short wake-up frame first.
Console readings
pwr
The console command that lists every battery of the stack, one line each: voltage, current, temperature, lowest and highest cell, state and charge. See every column explained.
bat
The command that lists the cells of one battery, with their voltage, temperature, state and balancing flag.
Charge, Dischg, Idle
The working states shown by the console: charging, discharging, or neither.
Absent
Shown for a stack position where the master sees no battery: either nothing is installed there, or a battery has dropped off the link.
Coulomb
In pwr, the state of charge in percent; in bat, the remaining capacity in mAh.
Tools
BatteryView
Pylontech's Windows service program for installers. See our BatteryView guide.
Viewer
Any tool that reads the battery through its CONSOLE port and shows the data in a readable way: BatteryView, our free online viewer, or a Wi-Fi box that puts it online from anywhere.
Datalogger
An add-on that some systems use to send battery data to a manufacturer's cloud. Plain US2000, US3000 and US5000 stacks don't have one built in.